Unified Controller nv series type2 light Controller Unit Instruction Manual
63
Table 6-3 Controller operation status and LED display
[Single operation]
Controller status
LED status
LED name RUN
ONL
STBY
HALT
ERR
ALM
BATT
TRK
Green
Green
Green
Green
red
Yellow
Green
Green
DL-WAIT
(Waiting for downloaded)
○ ○ ○
◎
○ ○
−
○
RUN
○
HALT(Halt)
ONL
RUN (Operation)
STBY
ERR (Error)
HALT
Minor failure
ERR
No battery is mounted or
the voltage is low.
−
○ ○
−
−
−
○ ○
ALM
○
The battery is normal.
BATT
TRK
●: ON,
◎
: Flash, ○: Off,
−
: No association between the controller status and LED status
(Note) Confirm ERR on the error log.
[Duplex operation]
Controller status
LED status
LED name RUN
ONL
STBY
HALT
ERR
ALM
BATT
TRK
Green
Green
Green
Green
Red
Red
Green
Green
DL-WAIT
(Waiting for downloaded)
○ ○ ○
◎
○ ○
−
○
HALT(Halt)
ODD-RUN
(Single operation)
● ● ○ ○ ○
−
−
○
RUN
○
MASTER-RUN
(Online operation)
● ● ○ ○ ○
−
−
◎
ONL
○
SLAVE-RUN
(Standby operation)
● ○ ● ○ ○
−
−
◎
STBY
○
EQL-SEND-RUN-
(Equalization transmission)
●
◎
○ ○ ○
−
−
○
HALT
○
EQL-RCV-RUN
(Equalization receiving(
● ○
◎
○ ○
−
−
○
ERR
○
ERR (Error)
ALM
Minor failure
BATT
No battery is mounted or
the voltage is low.
−
−
−
−
−
−
○ ○
TRK
○
The battery is normal.
●: ON,
◎
: Flash, ○: Off,
−
: No association between the controller status and LED status
(Note) Confirm ERR on the error log.
About the checking method,
refer to “7.2 Trouble Details Checks” in this manual.
About the function of controller module, refer to 6F8C1576
「
Unified Controller nv Series type 2
light Function Manual
」