E6581528
F-33
6
[Timing chart (example)]
Set frequency
Commercial power/inverter switching frequency

MC output for inverter operation
Commercial power/inverter switching output 1
(P24-OUT1)
MC output for commercial power operation
Commercial power/inverter switching output 2
(P24-OUT2)
Commercial
p
ower switchin
g
si
g
nal
(
S3-CC
)
ON
Commercial power-side switching
waiting time

Inverter-side switching waiting
time

Detection time
Commercial power switching frequency
holding time

ON
ON
ON
Commercial power switching signal S3-CC ON : Commercial power operation
Commercial power switching signal S3-CC OFF : Inverter operation
Title Function Adjustment range Example of setting

Commercial power/inverter switching output selection
~ or
 Commercial power/inverter switching frequency ~Hz Power supply frequency etc.
 Inverter-side switching waiting time ~
sec.
According to model
Refer to page K-46.
 Commercial power-side switching waiting time ~
sec.


Commercial power switching frequency holding time
~
sec.

 Input terminal function selection 7 (S3) ~

(Commercial power switching)
 Output terminal function selection 1 (OUT1) ~ 

(Commercial power/inverter
switching output 1)
 Output terminal function selection 2 (OUT2) ~ 

(Commercial power/inverter
switching output 2)
- Warning -
When switching to commercial power, make sure that the direction in which the motor rotates when operated
on commercial power agrees with the forward direction when operated via the inverter.
Do not select any option (=) of  (reverse rotation prohibition selection) that prohibits forward
rotation. Or it becomes impossible to switch to commercial power, because the motor cannot rotate in the
forward direction.
6.20 PID control
 : PID control switching
 :
PID control feedback control signal selection
 : Delay filter
 : Proportional (P) gain
 : Integral (I) gain
 : PID deviation upper limit
 : PID deviation lower limit
 : Differential (D) gain
 : Process upper limit
 : Process lower limit
 : PID control waiting time
 : PID output upper limit
 : PID output lower limit
 : Process increasing rate
(speed type PID control)
 : Process decreasing rate
(speed type PID control)
For details, see Instruction Manual (E6581329) specified in Section 6.42.

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS1 and is the answer not in the manual?

Toshiba TOSVERT VF-AS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS1
CategoryInverter
LanguageEnglish

Related product manuals