5.15 Changing the display unit % to A (ampere)/V (volt)
 : Current/voltage unit selection
Example of setting
During the operation of the VFAS1-6022PL (rated current 4.0A) at the rated load (100% load), units are displayed
as follows:
1) Display in percentage terms 2) Display in amperes/volts



Output current:
4.0A
DC voltage:575
V
(Converted into AC
voltage)
DC voltage:100%
Output current:
100%



if

was set in

if was set in 
[Parameter setting]
Title Function Adjustment range Default setting
 Current/voltage unit selection
: %
: % A (ampere)/V (volt)

• Function
These parameters are used to change the unit of monitor display.
% A (ampere)/V (volt)
Current 100% = Inverter’s rated current
Voltage 100% = 500Vac ( if  is set in)
575Vac ( Default setting or if  is set in)
690Vac ( if  is set in)
* The  converts the following parameter settings:
A display Current monitor display
Setting of electronic thermal protection level 1/2/3/4 , , , , 

DC braking current 
Stall prevention level 
V display Voltage monitor display
V/f 5-point setting , , , , 
Note: Base frequency voltage 1~4 (, , , ) is always displayed in the unit of V.