E6581528
E-10
5
4) Setting the run, stop and operation frequencies (forward run, reverse
run and coast stop) by means of external signals (default setting)
Title Function Example of setting

Command mode
selection
:(Terminal input)

Frequency
setting mode
selection 1
(VI/II (voltage/current input) )
(RR/S4
(potentiometer/voltage
input) )
(RX (voltage input) )
Run/stop :ON/OFF of terminals F-CC/R-CC
Speed command :External signal input
(1) VI/II terminal: 0~+10Vdc
(0~+5Vdc) or
4(0)~20mAdc
(2) RR/S4 terminal: Potentiometer
0~+10Vdc (0~+5Vdc)
(3) RX terminal: 0~±10Vdc (0~±5Vdc)
Moto
r
IM
R/L1
Power
supply
S/L2
T/L3
U/T1
V/T2
W/T3
(1) 0~+10Vdc
(0~+5Vdc)
or 4(0)~20mAdc
(3) 0~±10Vdc
(0~±5Vdc)
(2) External potentiometer
-
-
+
+
* Other speed setting
: 2-wire RS485 input
: 4-wire RS485 input enabled
: Communication option input enabled
*
: Optional AI1 (Differential current
input)
*
: Optional AI2 (voltage/current input) *

: Up/Down frequency

: RP pulse input
*

: High-speed pulse input
*

:-
* Commands marked with * are
optional. Refer to Instruction Manual
of options described in Section 10.
CCA RX VI/II
RR/S4
PP
Inverter
+
The inverter is factory-
configured so that, if F and
R are turned on at the
same time, the inverter will
stop operation. If
necessary, the direction of
rotation can be reversed
by changing parameter
settings.
Refer to Section 6.2.1.
ON:Reverse run,
OFF:Deceleration stop
F
R
CC
ON:Standby,
OFF:Coast stop
(Set the parameters

to
and

to
to
assign the standby signal
input function to the S3
terminal.)
S3
ON:Forward run,
OFF:Deceleration stop
PWR
P24/PLC