EasyManua.ls Logo

Trane BCHC - Analog Inputs; Binary Input Configurations; Binary Inputs; Binary Outputs

Trane BCHC
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BCXC-SVX01A-EN 39
Operation
Sequence of
Operation
Analog Inputs
See Table O-SO-11 on page 40 for a
complete description of analog inputs.
Binary Outputs
Binary outputs are configured to support
the following:
• Two fan stages (when one or two fan
stages are present, J1-2 can be
configured as exhaust fan)
• One hydronic cooling stage
• One hydronic heating stage
(dehumidification requires this to be in
the reheat position)
• One DX cooling stage
• One or two-stage electric heat
(dehumidification requires this to be in
the reheat position)
• Face and bypass damper
• Modulating fresh air damper (Tracer
ZN520 only)
• One-stage baseboard heat
Table O-SO-10. Binary Input Configurations
Binary Controller Operation
Input Description Configuration Contact closed Contact open
BI 1 Low temperature NC normal diagnostic
detection (Note 1) (note 5)
BI 2 Condensate overflow NC normal diagnostic
(Note 1) (note 5)
BI 3 Occupancy NO unnnoccupied occupied
BI 3 Generic binary input NO normal (note 3) normal (note 3)
BI 4 Fan status (Note 1) NO normal diagnostic
Note 1: During low temperature, condensate overflow, and fan status diagnostics, the Tracer
®
ZN520 control disables all
normal unit operation of the fan, valves, and damper.
Note 2: The occupancy binary input is for standalone unit controllers as an occupied/unoccupied input. However, when the
controller receives a communicated occupied/unoccupied request, the communicated request has priority over the
hardwired input.
Note 3: The generic binary input does not affect unit operation. A building automation system reads this input as a generic
binary input
Note 4: If the fan mode input is in the off position or the controller is in the unoccupied mode with the fan off, the fan
status input will be open. A diagnostic will not be generated when the controller commands the fan off. A diagnostic
will only be generated if the fan status input does not close after one minute from energizing a fan output or any time
the input is open for one minute. The controller waits up to one minute after energizing a fan output to allow the
differential pressure to build up across the fan.
Note 5: The table below shows the controller’s response to low temperature detection, condensate overflow, and fan
status diagnostics.
BIP Description Fan Valve Electric heat Damper
BI 1 Low temperature detection off open off closed
BI 2 Condensate overflow off closed off closed
BI 4 Fan status off closed off closed
Binary Inputs
Tracer ZN controllers have the following
binary inputs, factory-configured for the
following functions:
• Binary input 1: low temperature
detection (freezestat)
• Binary input 2: condensate overflow
• Binary input 3: occupancy/ generic
• Binary input 4: fan status (Tracer ZN520
only)
Note: The generic binary input can be
used with a Tracer Summit
®
building
automation system only.
BIP1: Low Temperature Detection
Option
The factory hard wires the low
temperature detection sensor to binary
input #1 (BIP1) on the Tracer ZN
controller. The sensor defaults normally
closed (N.C.), and will trip off the unit on a
low temperature diagnostic when
detecting low temperature. In addition,
Tracer ZN controls unit devices as listed
below:
Fan: Off
Valves: Open
Electric heat: Off
Damper: Closed
Note: See the “Diagnostics” section for
more information.
BIP2: Condensate Overflow Detection
Option
The factory hard wires the condensate
overflow sensor to binary input #2 (BIP2)
on the Tracer
ZN controller. The sensor
defaults normally closed (N.C.), and will
trip off the unit on a condensate overflow
diagnostic if condensate reaches the trip
point. In addition, Tracer
ZN controls unit
devices as listed below:
Fan: Off
Valves: Closed
Electric heat: Off
BIP3: Occupancy Sensor
Binary input #3 (BIP3) on Tracer
ZN is
available for field- wiring an occupancy
sensor, such as a binary switch or a
timeclock, to detect occupancy. The
sensor can be either normally open or
normally closed. Reference Table 6.
BIP4: Fan Status (ZN520 Only)
Binary input #4 (BIP4) on Tracer
ZN is
available for sensor, such as a binary
switch or a timeclock, to detect
occupancy. The sensor defaults normally
open but can be configured as either
normally open or closed.

Table of Contents

Other manuals for Trane BCHC

Related product manuals