22 CG-SVX17D-EN
General Data
Table 7. General Data – 50 Hz – SI
Size 20 26 30 35 40 52 60 70 80 90 100 110 120
Compressor
Number#2222444444444
Tonnage/circuit¹ 10+10 13+13 15+15 15+20 10+10 13+13 15+15 15+20 20+20 20+25 25+25 25+30 30+30
Evaporator
Water storage (l) 5.3 8.3 8.3 12.1 9.1 15.5 18.9 28.4 26.5 34.1 39.0 43.5 43.5
Min. flow² (l/s) 1.2 1.6 1.8 2.1 2.4 3.1 3.6 4.2 4.9 5.5 6.2 6.7 7.2
Max. flow² (l/s) 3.7 4.8 5.4 6.2 7.3 9.4 10.8 12.6 14.8 16.5 18.7 20.2 21.6
Water connection (mm) 50.8 63.5 63.5 63.5 76.2 76.2 76.2 76.2 101.6 101.6 101.6 101.6 101.6
Condenser
Quantity of coils#1111222244444
Coil length (mm) 2311 2311 3226 3226 2311 2311 3226 3226 3073 3073 3658 3658 3658
Coil height (mm) 1727 1727 1727 1727 1727 1727 1727 1727 1067 1067 1067 1067 1067
Number of rows#2222222233333
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Quantity#2233446666888
Diameter (mm) 732 732 732 732 732 732 732 732 732 732 732 732 732
Airflow/fan
(m³/
h)
13245 13223 12890 12895 13244 13254 12890 12895 13298 13302 12748 12751 12753
Power/motor (kW) 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Motor RPM (rpm) 700 700 700 700 700 700 700 700 700 700 700 700 700
Tip speed (m/s) 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8
General Unit
Refrig circuits#1111222222222
Capacity steps % 50-100 50-100 50-100 43-100
25-50-
75-100
25-50-
75-100
25-50-
75-100
21-43-
71-100
25-50-
75-100
22-44-
72-100
25-50-
75-100
23-45-
73-100
25-50-
75-100
Refrig charge/
circuit¹
(kg) 15.4 15.4 21.8 21.8 14.5 14.5 21.8 21.8 33.6 33.6 40.9 39.0 38.1
Oil charge/circuit ¹ (l) 6.4 6.4 13.2 14.0 6.4 6.4 13.2 14.0 14.4 15.1 15.5 16.3 16.7
Min ambient
Wide ambient (°C) -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18
1. Data shown for circuit one only. The second circuit always matches.
2. Flow limits are for water only.