CG-SVX17D-EN 11 3
Controls Interface
Settings Screen
The Settings screen provides a user the ability to adjust settings necessary to support daily tasks.
The layout provides a list of sub-menus, organized by typical subsystem. This organization allows
each subscreen to be shorter in length which should improve the user's navigation.
A sample Settings screen is a list of the subsystems as shown below.
Settings Sub-Screens - Table of Text, Data, Ranges, etc.
Below is the table of text, resolution, field size, enumerated selections, and data for Settings
subscreens. See the functional specification “CGAM Settings and Setpoints” for further
information such as ranges and operation.
Table 41. Unit
Description Resolution or (Enumerations) Units
Front Panel Cool Cool Enum
Front Panel Chilled Water Setpt: + or - XXX.X Temperature
Auxiliary Chilled Water Setpt: + or - XXX.X Temperature
Front Panel Demand Limit Setpt: XXX Percent
Front Panel Ice Build Cmd: On/Auto Enum
Front Panel Ice Term Setpt: + or - XXX.X Temperature
Front Panel Noise Stb Cmd: On/Auto Enum
Setpoint Source:
(BAS/Ext/FP, Ext/ Front Panel, Front
Panel), BAS/Ext/FP
Enum
Table 42. Feature Settings
Description
Resolution or (Enumerations),
Default Units
Power-Up Start Delay: 10 seconds Seconds (MM:SS)
Cool Low Ambient Lockout: (Enable, Disable), Enable Enum
Cool Low Ambient Lockout Stpt: + or - XXX.X Temperature
Water Pump Off Delay: 1 minute Minutes (HH:MM)
Ice Building: (Enable, Disable), Disable Enum
PHR Fan Control: (Enable, Disable), Disable Enum