108
RT-SVX24Q-EN
Table 46. Service test guide for component operation part I of II (continued)
Component
Being Tested
COMPONENT CONFIGURATION
Supply
Fan
Return
Fan
Exhaust
Fan
Condenser
Fans
Heat Stages Compressor Stage
1 2 3 1 2 3 4 5
2A OFF OFF OFF
1A-Off/1B-
Off/1C-Off/
1D-Off 2A-
On /2B-Off/
2C-Off & 2D-
Off
OFF OFF OFF OFF OFF OFF OFF
N/A
2B & 2C OFF OFF OFF
1A-Off/1B-
On/1C-Off/
1D-Off 2A-
Off/2B-On/
2C-On/ 2D-
Off
OFF OFF OFF OFF OFF OFF OFF
N/A
2D OFF OFF OFF
1A-Off/1B-
On/1C-Off
1D-Off 2A-
Off/2B-Off/
2C-Off/ 2D-
On
OFF OFF OFF OFF OFF OFF OFF
N/A
100, 118, 128, 140, 162 Ton Evaporative Condensing
1A OFF OFF OFF
1A 0 -100 %
2A OFF
OFF OFF OFF OFF OFF OFF OFF
N/A
2A OFF OFF OFF
1A OFF 2A 0
- 100%
OFF OFF OFF OFF OFF OFF OFF
N/A
SUPPLY FAN ON ON OFF ALL OFF OFF OFF OFF OFF OFF OFF OFF
N/A
RETURN FAN ON ON
N/A
ALL OFF OFF OFF OFF OFF OFF OFF OFF
N/A
EXHAUST FAN OFF
N/A
ON ALL OFF OFF OFF OFF OFF OFF OFF OFF
N/A
GAS HEAT
(Full Capacity)
ON ON OFF ALL OFF ON ON ON OFF OFF OFF OFF
N/A
STAGE 1 ON ON OFF ALL OFF ON OFF ON OFF OFF OFF OFF
N/A
STAGE 2 ON ON OFF ALL OFF OFF ON
N/A
OFF OFF OFF OFF
N/A
Full Modulating
ON ON OFF ALL OFF 10% - 90% OFF OFF OFF OFF
N/A
ELECTRIC HEAT ON ON OFF ALL OFF ON ON ON OFF OFF OFF OFF
N/A
Stage 1
ON ON OFF ALL OFF ON OFF OFF OFF OFF OFF OFF
N/A
Stage 2
ON ON OFF ALL OFF OFF ON OFF OFF OFF OFF OFF
N/A
Stage 3
ON ON OFF ALL OFF OFF OFF ON OFF OFF OFF OFF
N/A
HYDRONIC HEAT OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF
N/A
OUTSIDE AIR
DAMPERS
OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF
N/A
EXHAUST
DAMPERS
OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF
N/A
EVAP COND
N/A
Sump Pump
OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF
N/A
Sump Heater
OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF
N/A
Table 47. Service test guide for component operation part II of II
Component
Being Tested
Component Configuration
Occ
Unocc
Relay
Sump Pump
Sump
Heater
Econo
Damper
Exhaust
Damper
VFD Output
COMPRESSOR
90 - 105 Ton
1A Closed Closed 0% Default OFF OFF
1B Closed Closed 0% Default OFF OFF
2A Closed Closed 0% Default OFF OFF
2B Closed Closed 0% Default OFF OFF
120 - 162 Ton
1A Closed Closed 0% Default OFF OFF
1B Closed Closed 0% Default OFF OFF
2A Closed Closed 0% Default OFF OFF
2B Closed Closed 0% Default OFF OFF
CONDENSER FANS
90 - 105 Ton Air Cooled
UUnniitt SSttaarrttuupp