RT-SVX24Q-EN
201
Table 77. Supply and exhaust/return fan VFD programming parameters
Menu ID Name FC DDP Unit
Operation/Display
0-01
Language English US English US
0-03
Regional Settings
North America North America
0-06 (TR150 only) Grid Type
Set to applicable unit power supply 200-240V/60Hz for
200 & 230V/60Hz units; 440-480V/60Hz for 460V/
60Hz units; 525-600V/60Hz for 575V/60Hz units; 380-
440V/50Hz for 380 & 415V/50Hz supply.For IT Grid (no
ground connections) or corner-grounded Delta power
supply systems, select the applicable voltage/Hz and
IT-Grid or Delta.
0-20 (TR200 only) Display Line 1.1 Small Analog Input 53 Analog Input 53
0-22 (TR200 only) Display Line 1.3 Small Input Power [hp] Input Power [hp]
0-40
[Hand on] Key on LCP
Disabled Disabled
Load and Motor
1-03
Torque Characteristics Variable Torque Variable Torque
1-20 (TR150)1-21
(TR200)
Motor Power [HP] Per Motor Nameplate HP
Sum of HP Per Motor
Nameplate HP [dual
motors on 60-75T]
hp
1-22
Motor Voltage
Per Motor Nameplate
Voltage
Per Motor Nameplate
Voltage
V
1-23
Motor Frequency Per Motor Nameplate Per Motor Nameplate
Hz
1-24 Motor Current
Per Motor Nameplate FLA
Sum of FLA Per Motor
Nameplate FLA [dual
motors on 60-75T]
A
1-25
Motor Nominal Speed
Per Motor Nameplate
Rated Speed
Per Motor Nameplate
Rated Speed
RPM
1-39 Motor Poles 4
6 if Motor Nameplate
Rated Speed ~1200 RPM4
if Motor Nameplate Rated
Speed > 1200 RPM
1-73
Flying Start
Enabled Enabled
1-90
Motor Thermal
Protection
ETR Trip1 ETR Trip1
Brakes
2-00
DC Hold/Preheat
Current
0 0 %
2-01 DC Brake Current 0 0 %
2-04
DC Brake Cut In Speed
[Hz]
10 10 Hz
Reference / Ramps
3-03 Maximum Reference 60 83 Hz
3-16 Reference 2 Source No function No function
3-17 Reference 3 Source No function No function
3-41
Ramp 1 Ramp up Time
30 30 s
3-42
Ramp 1 Ramp Down
Time
30 30 s
Limits / Warnings
4-12
Motor Speed Low Limit
[Hz]
22 15 Hz
4-14
Motor Speed High
Limit [Hz]
60 83 Hz
4-18 Current Limit 100 100 %
4-19
Max Output Frequency
60 120 Hz
SSeerrvviiccee aanndd MMaaiinntteennaannccee