INSTRUCTION MANUAL
UG30 CONTROL
18 (44)
mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN
The functions associated with the keys can be disabled by setting the USER Hi=1 parameter (see paragraph
“ACCESS TO PARAMETERS WHILE CONSULTING OR PROGRAMMING”).
GLb GENERAL INFORMATION
Minimum Maximum Measurement
unit
Default
Hi
Prevents unauthorised operators from modifying parameters (the “padlock”
symbol is shown).
0 = no lock
1= lock out of all functions for modifying parameters, and resetting alarms
and hour-counters (except access to the USER password and keyboard
power down) – the padlock symbol is shown on the display).
0 1 flag 0
INFORMATION ON DISPLAY WHEN UNIT IS OFF
STATUS MASK
When the unit is powered up but not running, the STATUS MASK is shown on the display indicating the following
active fields:
A. Room temperature, room relative humidity (with humidity sensor only);
B. The indication:
• “
” and " ": unit turned OFF from a remote contact or a
Supervisor;
• "
unit turned OFF according to set hour bands.
C. Unit turned OFF due to alarm status:
MENU
PARAMETER
DESCRIPTION