98
CVZT TStat
CVZT ZS
VVZT ZS
VVZT TStat
System
X X X X Arbitration Method Request Enable External / BAS Control,
*Standalone Control
X X X X Emergency Override BAS
*Normal, Pressurize, Depressurize,
Purge, Shutdown
X X Heat Cool Mode Request Auto
X X Occupancy Request Auto
X X Occupied Bypass Time 120
X X Occupied Standby Cooling
Setpoint BAS
78
X X Occupied Standby Heating
Setpoint BAS
67
X X Space Cooling Setpoint High
Limit BAS
90
X X Space Cooling Setpoint Low
Limit BAS
50
X X Space Heating Setpoint High
Limit BAS
80
X X Space Heating Setpoint Low
Limit BAS
50
X X Supply Fan Configuration
Command
Continuous / Cycling
X X Timed Override Request
*Idle
X X X X Unit Stop Command
Stop/*Auto
X X Unoccupied Cooling Setpoint 85
X X Unoccupied Heating Setpoint 60
X VVZT DAT Control Mode
*Auto / Manual