CVZT
TStat
CVZT ZS
VVZT ZS
VVZT
TStat
Indoor
X X X X Filter Runtime Hours Setpoint
*0
X X Supply Fan Maximum Speed
Setpoint (vfd)
100%
X X Supply Fan Minimum Speed
Setpoint (vfd)
0%
X X X X Supply Fan Speed Command
*0%
X X X X Supply Fan Speed Command
Enable
Enabled/*Disabled (you can run the fan
here with no call)
X VVZT DAT Control Mode
Manual/*Auto
Refrigeration
X Compressor Cooling P-Gain (%/F) 80%
X Compressor Cooling P-Gain-1
(%/F)
2%
X Compressor Cooling P-Gain-2
(%/F)
5%
X Compressor Cooling Reset Time 500 sec
X Compressor Cooling Reset Time
1
1000 sec
X Compressor Cooling Reset Time
2
80 sec
X X X X Cooling Capacity Enable default 100%
X X X X Cooling Capacity Setpoint BAS you can run the cooling here with no
call - default 0%
X X X X Cooling Capacity Setpoint Enable
BAS
Enabled/*Disabled
X X X X Cooling Demand Limit Capacity
Enable Setpoint
Set to 0% for EDC Switch
X X X X Cooling Lockout BAS
Locked out / *Normal
X Discharge Air Cooling Setpoint
(Target)
55
X Discharge Air Temperature
Maximum Cool Limit
104
X Discharge Air Temperature
Minimum Cool Limit
50 (DACR POT)