EasyManua.ls Logo

turck BL20-PG-EN-V3 - Connectors; Fieldbus Connection

turck BL20-PG-EN-V3
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware description
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
16
Modbus TCP
Address assignment Static IP, BOOTP, DHCP
Supported Function Codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
Input data size max. 1024 registers
Input register start address 0 (0x0000 hex)
Out data size max. 1024 registers
Output register start address 0 (0x0000 hex)
EtherNet/IP™
Address assignment according to EtherNet/IP™ standard
Input data size 248 INT
Out data size 248 INT
PROFINET
Address assignment DCP
Conformance Class B (RT)
MinCycleTime 1 ms
Diagnostics according to PROFINET Alarm Handling
Topology detection supported
Automatic address assignment supported
Input data size max. 512 byte
Out data size max. 512 byte
Ambient conditions
Operating temperature -40…+70 °C
Temperature derating
> 55 °C Derating: max. field supply current = 5 A
Storage temperature -40…+85 °C
Relative humidity 15 to 95% (internal), Level RH-2, no condensation
(at 45 °C storage)
Vibration test according to EN 61131
up to 5 g (at 10 to 150 Hz) for mounting on DIN rail no drilling according to EN 60715,
with end bracket
up to 20 g (at 10 to 150 Hz) for mounting on base plate or machinery Therefore every sec-
ond module has to be mounted with two screws each.
Shock test according to IEC 68-2-27
Drop and topple according to EN 68-2-31 and free fall according to IEC 68-2-32
Electro-magnetic compatibility according to IEC 61131-2
Protection class IP67
DIN rail mounting yes, please observe offset
Direct mounting two mounting holes, 6 mm Ø
General
Dimensions (w × l × h) 74 × 145 × 77.5mm
Approvals CE

Table of Contents

Related product manuals