3.6 Device addressing and operation mode setting
The device address and the operation mode are set using a combination of the 2 rotary coding
switches and the DIP switches at the device.
A „-“: Switch position is irrelevant
Fig. 7: Rotary coding and DIP switches at
BL20-PG-EN-V3
Fig. 8: Rotary coding and DIP switches at
BL67-PG-EN-V3
Rotary cod-
ing switches
DIP switches A Mode Description
5 (MODE)4321
00 1 0 0 - - Restore IP Reset the device to d
efault settings
(see page 20):
IP address 192.168.1.254
Subnet mask 255.255.255.0
gateway 192.168.1.1
Auto-negotiation/
AutoMDIX
active
QuickConnect/FSU inactive
40 1 ----DHCP Addressing via DHCP (see page 21)
50 1 - - - - PGM Addressing via PGM (see page 21)
60 1 - - - - PGM-DHCP Addressing via PGM-DHCP (see page 22)
State of delivery
90 1 - - - - F_Reset Reset to factory settings (see page 23)
1-99 0 - - - - Static
rotary
Sets the last byte of the IP address (see page 20).
The other 3 byte are taken from the IP address, which was
stored in the device before.
00 0 0 0 - - Address Sets the last byte of the IP address to 100.
The other 3 byte are taken from the IP address, which was
stored in the device before.
1 = 5 VDC
2 = D –
3 = D +
4 = GND