Programmable Gateways BLxx-PG-EN-V3
3.6.6 F_Reset (Reset to factory setting)
In order to reset the device to factory settings, the DIP-switch MODE is set to "ON", the rotary
switches to address "90" (see Device addressing and operation mode setting (page 19)).
This mode sets all device-settings back to the default values and deletes all data in the device's inter-
nal flash.
The following properties are reset to default or deleted during F_Reset:
NOTE
This setting is no operation mode! Please set the device to another mode after having
reset the IP address to the default values.
Default value Comment
IP address/
subnet mask
Reset 192.168.1.254/
255.255.255.0
The device can be accessed by the web
server/DTM using this IP address but the
address is not permanently stored in the
device.
PROFINET device name Reset -
CODESYS program deleted -
parameters (PG-V3) Reset see Parame-
ters (page 39)
Parameters of I/O-
modules
no
NOTE
Resetting the device to factory settings via DCP-based services (via Turck IP Address Tool
or TIA-Portal/Step7) does not delete the CODESYS-program (see also Reset to factory set-
tings (page 29).