Parameters and diagnostics
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
40
4.2 Diagnostics
4.2.1 System diagnostics
The system diagnostics can be called via the instance name of the "Local_IO_BLxx"-object. Function
blocks or libraries are not required.
Fig. 23: Diagnostics via call of instance
Diagnostics Meaning
Module diagnostics available
„xModuleDiagnosticsAvailable“
At least one module sends diag-
nostics.
Check the diagnostic messages.
I/O configuration deviation
„xI/OConfigurationDeviation“
I/O module list adaptable modi-
fied, e. g., module has been pulled.
The current and configured module list do
not match but the data exchange pro-
ceeds as normal.
Check the physical station for pulled or
new but not planned modules.
Check the system power supply at the
gateway.
Module bus error
„xModuleBusError“
The Communication with the
module bus station on the module
bus is not possible.
At least one module has to be plugged
and has to be able to communicate with
the gateway.
I/O configuration error
„xMasterOrIOConfigurationError“
The actual module list has been
changed and is incompatible, a
process data exchange with the
module bus nodes is not possible-
Compare the configured station and the
current configuration.
Check the physical station for defective
or incorrectly plugged electronic mod-
ules.