33
V01.0| 2016/04
Programmable Gateways BLxx-PG-EN-V3
3.9.2 LED description BL67
LED GREEN RED Meaning Remedy
IO
OFF OFF No power supply of the CPU. Check the system power supply at the gateway.
ON OFF Communication running.
The modules configured corre-
spond to the modules in the sta-
tion.
blinking,
1 Hz
OFF Station is in the Force Mode of the
I/O-ASSISTANT.
Deactivate the Force Mode of the I/O-ASSISTANT.
OFF ON CPU not ready for operation,
possible causes:
too many modules at the gateway
short-circuit in connected module
gateway hardware error.
Check the system power supply at the gateway
and the cabling.
Unmount excessively mounted modules.
Replace the gateway, if necessary.
OFF blinking,
1 Hz
Non adaptable changes in the con-
figuration of the module bus
nodes.
Compare the configured station and the current
configuration.
Check the physical BL67-station for defective or
incorrectly plugged electronic modules.
OFF blinking,
4 Hz
no communication
via the module bus.
At least one module has to be plugged and has to
be able to communicate with the gateway.
blinking, alternating The current and configured mod-
ule list do not match but the data
exchange proceeds as normal.
Check the physical station for pulled or new but
not planned modules.
Check the system power supply at the gateway.
OFF blinking
double
1 Hz
Device internal communication
disturbed
LED GREEN RED Meaning Remedy
GW
OFF OFF No power supply of the CPU. Check the system power supply at the gateway.
ON OFF Firmware active, gateway ready
OFF blinking Wink-command received
Deactivate an active WINK-command
LED GREEN RED Meaning Remedy
RUN
OFF OFF No power supply of the CPU. Check the system power supply at the gateway.
ON OFF PLC program running -
blinking OFF Firmware updated running see Firmware update
OFF ON PLC program stopped
OFF blinking No PLC program loaded
OFF blinking,
1 Hz
F_Reset is in progress see page 23
LED GREEN RED Meaning Remedy
V
I
/V
O
OFF OFF Supply voltage too low Check the system power supply at the
gateway.
ON OFF V
I
and V
O
within the nominal range
blinking, 1
Hz
OFF Undervoltage V
I
; system running. Check the system power supply at the
gateway.
blinking, 4
Hz
OFF Undervoltage V
O
; system running.
ON
(orange)
ON Sensor supply current (I
SENS
) too high
LED GREEN RED Meaning
APPL
This LED is controlled by the CODESYS program and can be freely programmed by the user.