USB Host port functions
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
64
Restore 2 RESTORE_2 Loading the CODESYS application and further device from the
storage device into the BLxx-PG-EN-V3.
The following files are loaded from the storage device:
– All *.app and *.crc files.
– PlcLogic folder
– Folder USB_Data
– IP address
– PROFINET device name
– Retain-data (retain.bin)
The folder must contain only one application file (*.app).
All other applications on the device except for the retain data are
deleted without further warnings. The reatin data will only be
overwritten if the storage device contains a newer file.
The device automatically executes a restart after unplugging the
storage device.
STOP YES
Firmware update FW_UPDATE Update of the device firmware. The IP address, the PROFINET
device name and the CODESYS application will not be overwrit-
ten.
File name:
BLxx-PG-EN_1234567_Vx.y.z.0.bin
The device automatically executes a restart after unplugging the
storage device.
STOP YES
Write user data USB_DATA
_WRITE
Loading the folder "USB_Data"from the storage device into the
device.
Existing files with the same name will be overwritten. All other
data remain unchanged.
STOP YES