21 of 35 REF: CCU3/C-4100.DOC REV: M September 26, 2005
6. Configuring XL Graphics C/S.
6.1. Address Format
XL Graphics supports a wide number of Fire Indicator Panels on the SAME SYSTEM.
This means that a wide number of device address formats are supported. You need to
enter the Address Formats required for a 4100 Panel.
For connection to a 4100 interface for a standalone or networked fire panel add the
Address Formats as follows:
1. Run XL Graphics Maintenance
2. Click on Project
3. Click on Default Properties
4. Click the Device Address Formats ‘…’ button and enter in the following lines if they
are not already included in the Address Formats List.
For Logical address formats use:
nnn
nnn-nn
nnn-nn-nnn
nnn-nn-nnn-nnn
nnn-nn-nnn-nnn-nnn
For Symbolic address formats use:
nnn
nnn-nn
nnn-nn-nnn
nnn-nn-nnn-nnn
nnn-nn-nnn-nnn-nnn
nnn-nn-ZNnnn
nnn-nn-SIGnnn
nnn-nn-AUXnnn
nnn-nn-FBnnn
nnn-nn-IOnnn
nnn-nn-Mnnn-nnn
nnn-nn-Pnnn
nnn-nn-Annn
nnn-nn-Lnnn
nnn: CCU address
nnn-nn: Panel address (This can be 3 digit depending on what you set Panel
Number property in CCU3-4100 icon in XLMaintenance.)
nnn-nn-nnn: Card address
nnn-nn-nnn-nnn: Point address
nnn-nn-nnn-nnn-nnn: Sub-point address