EasyManua.ls Logo

Uponor Smatrix Pulse - Page 39

Uponor Smatrix Pulse
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
uponor.com l 37
Menu 05: High Floor Temperature Limitation
Default: 78°F (26°C)
Setting range: 38 – 95°F (20 – 35°C), 1°F (0.5°C) increments
Note
This parameter cannot be set lower than the set
value in settings Menu 06 (low floor temperature
limitation).
In this menu, a limit on the highest allowable floor
temperature is set. This menu is only visible if control
mode RFT is activated in Menu 04. For systems with a
Communication Module, this menu only shows the set
value. Changes are done in the Smatrix Pulse App.
Menu 06: Low Floor Temperature Limitation
Default: 68°F (20°C)
Setting range: 50 - 86°F (10 – 30°C), 1°F (0.5°C) increments
Note
This parameter cannot be set higher than the set
value in settings Menu 05 High floor temperature
limitation.
In this menu a limit on the lowest allowable floor
temperature is set. This menu is only visible if control
mode RFT is activated in Menu 04. For systems with a
Communication Module, this menu only shows the set
value. Changes are done in the Smatrix Pulse App.
Menu 07: Cooling Allowed
This menu sets whether a room will receive cooling or not.
This menu is not visible if a Communication Module is
connected to the system. The setting is then available in
the Smatrix Pulse App.
Menu 08: Display Units
This menu sets the temperature information in °F or °C.
Menu 09: Relay Module Integration
Use this menu to link a thermostat to a Relay Module for
controlling a forced-air heating and cooling system or fan
coil unit.
Menu 11: Room Temperature Calibration
Default: 0.0
Setting range: -6.0 – 6.0, 0.1 increments
This menu adjusts the temperature in the display if there
is a difference between the displayed versus the actual
temperature.
Menu 12: Invert Screen
This menu inverts the color in the display. The background
is black, and the numbers and icons are white.
Relative Humidity
The Digital Thermostat (T-169) also displays the relative
humidity level in the room or space. Pressing the OK button
three (3) times will display the following information:
Reference Description
A Relative humidity
B Relative humidity reading
Table 9-10: Relative humidity displays
Mini Sensor (T-161) Operation
During normal operation, the thermostat settings and
control is performed via the Uponor Smatrix App (requires
the Communication Module).
Reference Description
A Status LED
B Registration button
C Battery CR
D 2032V terminals for external sensor
Table 9-11: Mini Sensor (T-161) components
Figure 9-7: Relative Humidity
Figure 9-8: Mini Sensor (T-161) operation

Related product manuals