68 Installation and maintenance instructions 0020308121_04
Diagnostics code Values
Unit Increment, select, explanation
Setting
Min. Max. Factory Current
D.058
Solar circuit post-heating
3 5 3: Min. target DHW val. 60 °C
5: Auto
Outlet temperature 40 °C:
– At an inlet temperature ≤ 35 °C,
the heat generator starts in order
to reach the set outlet temperat-
ure.
– At an inlet temperature > 35 °C,
the heat generator stops or does
not start. If the inlet temperature
is < 30 °C, the heat generator
starts again.
Outlet temperature 60 °C:
– At an inlet temperature ≤ 55 °C,
the heat generator starts in order
to reach the set outlet temperat-
ure.
– At an inlet temperature > 55 °C,
the heat generator stops or does
not start. If the inlet temperature
is < 50 °C, the heat generator
starts again.
Only for products with integrated
domestic hot water generation.
5
D.060
Number of overheating faults
Current value
D.061
Number of ignition faults
Current value
D.062
Night set-back
0 30 ℃ 1 0
D.064
Average ignition time
Current value s
D.065
Maximum ignition time
Current value s
D.066
Warm start activation
Warm start deactivated
Warm start activated
Product-
dependent
D.067
Remaining burner anti-cycling time
Current value min
D.068
Number of unsuccessful ignitions at
1st attempt
Current value
D.069
Number of unsuccessful ignitions at
2nd attempt
Current value
D.070
3-port valve setting
0 2 0: Auto
2: Heating position
Only for products without integrated
domestic hot water generation.
0
D.071
Maximum target flow temperature
40 80 ℃ 1 75
D.072
Pump overrun after cylinder charging
0 10 min Internal pump 2
D.073
Offset: Target warm start value
-15 5 K 1 0
D.074
Anti-legionella function with integrated
cylinder
Off, On On
D.075
Maximum duration of the cylinder
charging
20 90 min 1 45