VAMP Ltd Arc protection system
User manual
VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316
39
13. Communication port for software programming
6.1.2. Control modes
The following control modes are available on the control panel
of the master unit:
RUN Normal operation
INSTALL System configuration
INFO Checking the system configuration
TEMP SET Setting and checking temperature limits
TEMP Reading measured temperatures
CURRENT Setting and reading start value and measured
values of the overcurrent unit
ERROR Reading and resetting internal fault memory
Choose a control mode by browsing up and down among the
modes using the up and down arrow buttons on the control
panel. The selected mode is indicated by the LED at the left
edge of the control panel.
NOTE!
The arc protection system is always ready for operation as long
as the auxiliary supply is switched on, independently of the
control mode of the master unit.
The master unit automatically returns to RUN mode in about
60 seconds after the last push of a button.
The modes RUN, INSTALL, INFO, TEMP SET and ERROR
can be set into an active state, where various measures can be
taken, such as setting system parameters, erasing messages,
etc. In normal state, system information can be read, but no
measures can be taken. In active state, the display is flashing
to indicate that the system is waiting for a command from the
operator.
To switch from normal to active state, press the S button. To
return from active state to normal state, press the S button
once again.
Figure 6.1.3-1 shows a fast guide to the functions available in
different control modes, in normal state as well as active state.