VAMP 260 Power monitoring unit
Operation and configuration
VAMP Ltd
16
Vamp 24h support phone : +358 (0)20 753 3264
VM260.EN004
3.2. Operating levels
The unit has three different operating levels: the User level,
the Operator level and the Configuration level. The purpose of
the operating levels is to prevent accidental change of unit
configurations, parameters or settings.
USER level
Use: Parameter values can be read
Opening: Level permanently open
Closing: Closing not possible
OPERATOR level
Use: Settings of protection stages can be changed
Opening: Default password 0001
Setting state:
On entering the parameter setting state a
password must be given, see 3.2.1
Closing:
The level is automatically closed when 10
minutes has elapsed since a key was pushed
or a setting was done via the local port. The
level can also be closed by giving the password
9999.
CONFIGURATION level
Use:
The configuration level is needed during the
commissioning of the unit.
Opening: Default password 0002
Setting state:
On entering the parameter setting state a
password must be given, see 3.2.1
Closing:
The level is automatically closed when 10
minutes has elapsed since a key was pushed
or a setting was done via the local port. The
level can also be closed by giving the password
9999.
3.2.1. Opening operating levels
1. Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 3.2.1-1. Opening an operating level