EasyManua.ls Logo

VAMP 260 - Analogue Outputs (Option); Auxiliary Voltage; Output Relays; Serial Communication Connection

VAMP 260
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VAMP 260 Power monitoring unit
Technical description
VAMP Ltd
30
Vamp 24h support phone : +358 (0)20 753 3264
VM260.EN004
4.2. Auxiliary voltage
The external auxiliary voltage Uaux (standard 40…260 V ac or
dc) for the unit is connected to the terminals X3: 17-18.
Note!
Polarity of the auxiliary voltage Uaux (24 V dc, option B):
- = X3:17 and + = X3:18.
4.3. Output relays
The power-monitoring unit is equipped with seven (five)
configurable output relays and a separate output relay for the
self-supervision system.
Trip relays T1 and T2 (terminals X3: 14-15 and 12-13)
Alarm relays A1 - A5 (terminals X3: 9-11, X2: 13-15, 10-12,
7-8, 5-6)
In the mA version of the PMU the alarm relays A4
(X2:7-8) and A5 (X2:5-6) are excluded.
Self-supervision system output relay IF (terminals X2: 16-
18)
4.4. Serial communication connection
X4: RS 232 serial communication connection for computers,
connector LOCAL (RS 232), connectors on front panel and
rear panel connected in parallel, see Figure 4-1.
X5: Remote control connection, connector REMOTE (TTL)
on the rear panel of the unit, see Figure 4-1.
4.5. Analogue outputs (option)
A terminal with the mA option has four configurable analogue
outputs that take up two of the output relays (A4 and A5).
Thus, a relay with the mA option has two output relays less
than the version without mA option.
The resolution of the analogue output is 12 bits resulting
current steps less than 6 µA. The output current range is
configurable allowing e.g. the following ranges: 0 .. 20 mA and 4
.. 20 mA. More exotic ranges like 0 … 5 mA or 10 … 2 mA can
be config-ured freely as long as the boundary values are within
0 … 20 mA.

Table of Contents