EasyManua.ls Logo

VAMP 52 - RI and RXIDG type inverse time operation

Default Icon
232 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical description 2 Protection functions 2.23 Inverse time operation
VM50.EN004 VAMP 24h support phone +358 (0)20 753 3264
107
RI and RXIDG type inverse time operation
These two inverse delay types have their origin in old ASEA
(nowadays ABB) earth fault relays.
The operation delay of types RI and RXIDG depends on the
measured value and other parameters according Equation
2.23.1-4 and Equation 2.23.1-5. Actually these equations can
only be used to draw graphs or when the measured value I is
constant during the fault. Modified versions are implemented
in the relay for real time usage.
Equation 2.23.1-4 RI
pickup
RI
I
I
k
t
236.0
339.0
Equation 2.23.1-5 RXIDG
pickup
RXIDG
Ik
I
t ln35.18.5
t = Operation delay in seconds
k = User’s multiplier
I = Measured value
I
pickup
= User’s pick up setting
Example for Delay type RI :
k = 0.50
I = 4 pu
I
pickup
= 2 pu
3.2
2
4
236.0
339.0
5.0
RI
t
The operation time in this example will be 2.3 seconds. The
same result can be read from Figure 2.23.1-15.
Example for Delay type RX
IDG:
k = 0.50
I = 4 pu
I
pickup
= 2 pu
9.3
25.0
4
ln35.18.5
RXIDG
t

Table of Contents

Related product manuals