Technical description 3 Supporting functions 3.5 Circuit breaker condition
monitorin
VM50.EN004 VAMP 24h support phone +358 (0)20 753 3264
123
Local panel parameters of CBWEAR function
Parameter Value Unit Description Set
CBWEAR STATUS
Al1L1
Al1L2
Al1L3
Al2L1
Al2L2
Al2L3
Operations left for
- Alarm 1, phase L1
- Alarm 1, phase L2
- Alarm 1, phase L3
- Alarm 2, phase L1
- Alarm 2, phase L2
- Alarm 2, phase L3
Latest trip
Date
time
Time stamp of the latest
trip operation
IL1
IL2
IL3
A
A
A
Broken current of phase
L1
Broken current of phase
L2
Broken current of phase
L3
CBWEAR SET
Alarm1
Current
0.00 100.00
kA Alarm1 current level Set
Cycles
100000
Alarm1 limit for
operations left
Set
Alarm2
Current
0.00 100.00
kA Alarm2 current level Set
Cycles
100000
Alarm2 limit for
operations left
Set
CBWEAR SET2
Al1On On
Off
'Alarm1 on' event
enabling
Set
Al1Off On
Off
'Alarm1 off' event
enabling
Set
Al2On On
Off
'Alarm2 on' event
enabling
Set
Al2Off On
Off
'Alarm2 off' event
enabling
Set
Clear
Clear
Clearing of cycle counters Set
Set = An editable parameter (password needed)
The breaker curve table is edited with VAMPSET.