Installation, Operating & Maintenance Instructions 
Series 650 DN 100-250 (I.D. 4“ - 10”), CC-Link 
 
 
 
VAT Vakuumventile AG, CH-9469 Haag, Switzerland 
Tel +41 81 771 61 61   Fax +41 81 771 48 30   CH@vatvalve.com www.vatvalve.com 
280672EB 
2010-12-15 
31/94 
 
3.1.1 Individual valve control 
 
This function is available on the Master valve only. 
It is possible to individually control any valve in the valve cluster. 
When commanding an individual valve to a certain position, make sure the target valve is set to ‘Freeze mode’ previously 
(refer to chapter «3.1.3 Freeze mode»), so it will listen to individually addressed commands and execute them. Once set 
to Freeze Mode the valve will execute any command addressed directly to it, until it is released from Freeze Mode. 
 
 
3.1.2 Individual valve status 
 
This function is available on the Master valve only. 
The Master valve holds a record of information about the status of the complete valve cluster. Therefore status information 
about all valves (Master and Slave(s)) connected to the valve cluster is available from the Master valve. Refer to chapter 
«INPUT Buffer» > «
CLUSTER VALVE STATUS bitmap» for details. 
 
 
 
3.1.3 Freeze mode 
 
This mode enables an individual valve to be controlled independent of the valve cluster. As soon as a valve is set to 
Freeze mode (freeze), it will remain in the last position it received from the Master valve before it was frozen. Now it is 
listening to commands addressed directly to it. Refer to chapter «OUTPUT Buffer (Master PLC)» > «Details» > 
«CLUSTER VALVE FREEZE CONTROL SETPOINT bitmap table» for details. 
 
Note: 
  The Freeze mode status is stored in a power save memory of each individual valve. In case valve was in freeze 
mode before power cycle (power off, power on), valve will stay in freeze mode after power up. 
 
  Valve will not accept freeze command when: 
1.  Digital input is active 
2.  Valve not yet synchronized 
 
  As soon as a valve is unfrozen, the valve starts to follow the Master valves plate position, meaning the plate 
might move immediately. 
 
 
 
3.1.4 Position offset 
 
The position offset can be used to add or subtract a certain offset value from the current position that is received from the 
Master valve. It might be helpful to compensate variations in pumping speed of the individual exhaust lines.  
 
Note: Position offset can be adjusted with CPA, CV or Service Box 2. 
 
Note: The position offset value will be stored in a power save memory of each individual valve.