Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4“ - 10”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
280672EB
2010-12-15
47/94
Local operation:
(‘Control View’, ‘Control Performance Analyzer’ or
‘Service Box 2‘)
Remote operation:
4. Do slave offline mode configuration
Go to ‘Tools / Terminal’ menu and use the following
commands
to change the configuration: [s:04][abcdefgh][CR][LF]
to read the configuration: [i:04][CR][LF]
Note: Each element is separated with square
brackets for clarity. Square brackets are not part of
command syntax. All elements are ASCII characters.
There are no spaces between the elements
necessary. Command is case sensitive
.
abcde reserved; do not change
f 0 = valve will close
1 = valve will open
2 = valve no change
gh reserved; do not change
5. Enable or disable ZERO function in menu
‘Setup / Sensor’.
6. Do sensor configuration in menu ‘Setup /
Sensor’.
Note: Read first current configuration and do not change reserved bits when sending new configuration.