Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4“ - 10”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
280672EB
2010-12-15
70/94
CLUSTER VALVE STATUS bitmap table:
This bitmap corresponds to the CLUSTER VALVE MONITORING ADDRESS.
Bit Description
0-1 ACCESS MODE
bit 1
bit 0
0 0
= LOCAL
0 1
= REMOTE
1 0
= LOCKED
2
FREEZE MODE
Valve is in freeze mode (the slave valve is separated from the cluster)
3
OFFLINE STATUS
No communication with cluster valve
4-7
NOT USED (reserved)
-
8
SERVICE REQUEST
Valve movement tight
9
COMPRESSED AIR
Compressed air pressure < 4 bar (only for valves with compressed air)
10
POWER FAILURE
BATTERY
Not ready, voltage too low
11-15
NOT USED (reserved)
-
CLUSTER VALVE WARNINGS bitmap table:
Bit Description
0
OUT OF RANGE:
CLUSTER VALVE
FREEZE POSITION
SETPOINT
Value of CLUSTER VALVE FREEZE POSITION SETPOINT is out of range
1
OUT OF RANGE:
CLUSTER VALVE
FREEZE ADDRESS
SETPOINT
Value of CLUSTER VALVE FREEZE ADDRESS SETPOINT is out of range
2
OUT OF RANGE:
CLUSTER VALVE
CONTROL SETPOINT
Value of CLUSTER VALVE CONTROL SETPOINT is out of range
3
OUT OF RANGE:
CLUSTER VALVE
MONITORING ADDRESS
SETPOINT
Value of CLUSTER VALVE MONITORING ADDRESS SETPOINT is out of range
4-7
NOT USED (reserved)
-