EMR3 Truck Installation 3-Way Safety Valve for Truck LP Gas Systems
31
3-Way Safety Valve for Truck LP Gas Systems
The 3-Way Safety Valve is not intended for flow control or preset control.
3-WAY VALVE INSTALLATION KIT
This kit does not contain conduit, hoses or fittings. The maximum operating pressure for
the valve is 250 psi, with a temperature range of -40 to +185°F (-40 to +85°C).
WARNING
The Three-Way Safety Valve is installed and operated in the highly
combustible environment of an LPG tank.
Fire or explosion resulting in serious injury or death could result if the
equipment is improperly installed or modified.
1. It is essential that you carefully read and follow the warnings and
instructions in this manual to protect yourself and others from serious
injury due to fire, explosion, or electrical shock. LPG systems shall be
installed in accordance with the national standards and regulations that
apply.
2. Comply with all federal, state, and local codes, and other applicable
safety codes. All wiring must comply with standard electrical practices,
the local authority, and the latest editions of the National Electrical Code
(NFPA 70) and other applicable code requirements. All work on LPG
systems must comply with NFPA 58, Liquefied Petroleum Gas Code and
other applicable code requirements.
3. LPG tanks must be depressurized (drained) and free of liquid and
combustible vapors before work begins.
4. Flow control valves connected to the EMR must either be Recognized
Components or UL Listed. Flow control valves must be suitable for the
intended application, i.e., gasoline, fuel oil, LPG, etc. For LPG
applications, such as propane, each valve must have a minimum
pressure rating of 250 psi.
Table 9.- 3-Way Valve Installation Kit 846000-028
Item Qty V-R P/N
3-Way Solenoid Valve 1 576008-654
Cord Grips 3 331028-001
Cable Seal Kit 1 330020-098
2-Wire Cable 50 feet (15.24 m) 848100-250
Wire Nuts 2 576008-461