EMR3 Terminal - Fueling Depot Installation Pulse Output for EMR3
54
FLOW RATE LIMITS BASED ON THE TYPICAL TIME IT TAKES THE IB TO SEND PULSES
Setting Max Flow Rate
0.1 pulse/gallon 250,000 gpm
1.0 pulse/gallon 25,000 gpm
10.0 pulses/gallon 2,500 gpm
100 pulses/gallon 250 gpm
1,000 pulses/gallon 25 gpm
Example:
Set the PULSES/VOL to 100 pulses per gallon. Deliver 3,000 gallons at a flow rate of 600 gpm. The actual
delivery takes 5 minutes, but it may take the EMR
3
another 7 minutes to transmit the last 175,000 pulses.
Consider both the flow rate and the time it takes to send all of the pulses prior to setting the PULSES/VOL value.