Appendix C: Typical Setup Parameters - TLS-350
C-2
*IMPORTANT: If Gilbarco T24 (BDIM) Site Controllers are to be interfaced to the gauge on a Non-24-Hour site,
this parameter should be set to DISABLED.
Line Ann Tst Needed Wrn Disabled Default
Line Ann Tst Needed Wrn Days Disabled Default
Line Ann Tst Needed Alm Days Disabled Default
Remote Printer Page Eject Disabled Default
Print TC Vol. Enabled Disable
Temp. Comp. 15.6 °C Enabled Default
Stick Height Offset Disabled Disabled
H Protocol Format Height Default
Precision Test Duration
Precision Line Test Auto-Confirm Enabled
Daylight Savings Time Enabled
MAR WK6 SUN 03:00AM
OCT WK6 SUN 04:00AM
Re-Direct Local Printout Disabled Default
QPLD Monthly Printout Enabled Default*
BDIM Transaction Delay 24 Default
Euro Protocol Prefix S Default
Security Code 000000 XXXXXX
Table C-2. Comm Board (1, 2, Etc.) Setup
Parameter Default Set As
Baud Rate 1200 Comm Rate for Third Party Equip.
Parity Odd Parity for Third Party Equip.
Stop Bit 1 Stop Default
Data Length 7 Data Default
Table C-1. System Setup
Parameter Default Set As

Table of Contents

Other manuals for Veeder-Root TLS-350