EasyManua.ls Logo

Veeder-Root TLS-HLD - Function Code: 205; In-Tank Status Report

Veeder-Root TLS-HLD
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
RS-232 Commands Function Code: 205
Function Code: 205
Function Type: In-Tank Status Report Version 1
Command Format:
Display: <SOH>I205TT
Computer: <SOH>i205TT
Typical Response Message, Display Format:
<SOH>
I205TT
TANK STATUS
1 ALL FUNCTIONS NORMAL
<ETX>
Typical Response Message, Computer Format:
<SOH>i205TT0000000000TTnnAA...
TTnnAA&&CCCC<ETX>
Notes:
1. 0000000000 - Unused
2. TT - Tank Number (Decimal, 00 = all)
3. nn - Number of alarms active for tank (Hex, 00 = none)
4. AA - Active tank alarm type:
01 = Unused
02 = Unused
03 = Unused
04 = Unused
05 = Tank Low Product Alarm
06 = Unused
07 = Unused
08 = Unused
09 = Tank Probe Out Alarm
10 = Unused
11 = Unused
12 = Unused
13 through 26 = Unused
27 = Tank Low Temperature Warning
5. && - Data Termination Flag
6. CCCC - Message Checksum

Table of Contents