42
RS-232 Commands Function Code: A02
Function Code: A02
Function Type: Probe Factory Dry Calibration Values Version 1
Command Format:
Display: <SOH>IA02TT
Computer: <SOH>iA02TT
Typical Response Message, Display Format:
<SOH>
IA02TT
TT PP CCC.CCCC
<ETX>
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. PP - Probe Type: 03 = MAG1
3. CCC.CCCC - Probe Data (Decimal)
Typical Response Message, Computer Format:
<SOH>iA02TT0000000000TT0PPNNFFFFFFFF...
TT0PPNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. 0000000000 - Not Used.
2. TT - Tank Number (Decimal, 00 = all)
3. 0 - Not used
4. PP - Probe Type: 03 = MAG1
5. NN - Number of eight character Data Fields to follow (Hex)
6. FFFFFFFF - Calibration Value (ASCII Hex IEEE float)
7. && - Data Termination Flag
8. CCCC - Message Checksum