EasyManua.ls Logo

Veeder-Root TLS-HLD - A02 Probe Calibration Values; Function Code: A02

Veeder-Root TLS-HLD
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
RS-232 Commands Function Code: A02
Function Code: A02
Function Type: Probe Factory Dry Calibration Values Version 1
Command Format:
Display: <SOH>IA02TT
Computer: <SOH>iA02TT
Typical Response Message, Display Format:
<SOH>
IA02TT
TT PP CCC.CCCC
<ETX>
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. PP - Probe Type: 03 = MAG1
3. CCC.CCCC - Probe Data (Decimal)
Typical Response Message, Computer Format:
<SOH>iA02TT0000000000TT0PPNNFFFFFFFF...
TT0PPNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. 0000000000 - Not Used.
2. TT - Tank Number (Decimal, 00 = all)
3. 0 - Not used
4. PP - Probe Type: 03 = MAG1
5. NN - Number of eight character Data Fields to follow (Hex)
6. FFFFFFFF - Calibration Value (ASCII Hex IEEE float)
7. && - Data Termination Flag
8. CCCC - Message Checksum

Table of Contents