56
Console Specifications TLS-HLD Probe Circuit Codes
TLS-HLD Probe Circuit Codes
Table 3 lists the probes that can be used with the console.
Table 3.- Mag Probe Minimum Detected Fluid Levels
Circuit
Code Mag Probe Type
Name
Plate
Color
Water
Detect
2” Floats
Min.
Fuel
Level
Min.
Water
Level
Mag Probes - Form Number 8473
C000 Std., 2 float Black Yes 9.5” 0.75”
C001 Std., 2 float Red Yes 9.5 0.75”
D000 Std., Inv. only, 2 flt Green Yes 9.5” 0.75”
D001 Alt., 1 float Black No 7”
D002 Alt., 1 float Red No 7”
D003 Alt., Inv. only Green No 7”
Mag Probes - Form Numbers 8463 & 8493
D004 2 float Black Yes 3.23” .867”
D005 2 float Red Yes 3.23” .867”
D006 Inv. only, 2 flt Green Yes 3.23 .867”
D007 1 float Black No 3”
D008 1 float Red No 3”
D009 Inv. only, 1 flt Green No 3”
Mag Probes - Form Number 8468
D021 Inv. only 2 flt Blue Yes 3.23” 0.867”
D022 Inv. only, 2 flt Blue Yes 3.23” 0.867”
D023 Inv. only, 1 flt Blue No 3