34
RS-232 Commands Function Code: 601
Function Code: 601
Function Type: Set Tank Configuration Version 1
Command Format:
Set:
Inquire:
Display: <SOH>S601TTf Display: <SOH>I601TT
Computer: <SOH>s601TTf Computer: <SOH>i601TT
Typical Response Message, Display Format:
<SOH>
I601TT
f
<ETX>
Typical Response Message, Computer Format:
<SOH>i601TT0000000000TTf...
TTf&&CCCC<ETX>
Notes:
1. 0000000000 - Not Used
2. TT - Tank Number (Decimal, 00 = all)
3. f - Tank Configuration Flag:
0 = Off
1 = On
4. && - Data Termination Flag
5. CCCC - Message Checksum

Table of Contents