RS-232 Commands Function Code: 608
35
Function Code: 608
Function Type: Set Tank Tilt Version 1
Command Format:
Set:
Inquire:
Display: <SOH>S608TTHHH.HH Display: <SOH>I608TT
Computer: <SOH>s608TTFFFFFFFF Computer: <SOH>i608TT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. HHH.HH - Tank Tilt, (Decimal)
3. FFFFFFFF - Tank Tilt, (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I608TT
TT HHH.HH
<ETX>
Typical Response Message, Computer Format:
<SOH>i608TT0000000000TTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. 0000000000 - Not Used.
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Tank Tilt, (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum