Troubleshooting Probe Diagnostic Menu
47
.
Table 1.- Diagnostics Menu
Menu Display Sequence Display Notes and/or Instructions
Diagnostics
Diagnostics
Press
Press
key to enter Diagnostics. You can also press the Print key to print
out the Diagnostic Report if you have made the correct comm setup selec-
tions and you have a serial printer connected.
Software Version
XXXXXX-XXX Y
Consoles current software version. Note: from this display on, you press
key to move from one display to the next.
T1: Probe Type:
GLB01
Probe type installed in tank (in this example, T1). At any ‘T’ display below,
press the Tank key to view equivalent data for other tanks.
T1: Serial Number
XXXXX
Serial number of the probe.
T1: Probe ID
XXXXX
Manufacturing code of the probe.
T1: Probe Length
XXX
Length of the probe.
T1: Gradient
XXX.XXXX
Probe calibration factor used to calculate water height and product height.
T1: Number Samples
20
Number of probe measurement sets made before posting water height,
product height, and product temperature. (A measurement set consists of
probe counts 00 - 18 discussed below.)
T1: Samples Read
XXXXXX
Historical total of probe measurements read.
T1: Samples Used
XXXXXX
Historical total of probe measurements used.
T1: Counts
00 XXXXX 01 XXXXX
Probe counts used to calculate water height, product height, and product
temperature. Counts 00 - 18 constitute one probe measure set.
(Continue to press the
key to move through
all of the count pairs until
you reach the last count
below)
T18: Counts
18 XXXXX