ID Title Description Default Range Unit
P1101
Secondary Loop Coolant
Type
Set secondary loop coolant
type
Water
Water
PG25
—
P1102 Primary Loop Coolant Type Set primary loop coolant type
1
Water
Water
PG25
—
1
Selection of PG25 equates to nominal 25% propylene glycol content.
Table 4.27 Configuration—Coolant
4.2.9 Service Screen
The Service screen is used to set some parameters and to assist during commissioning. This screen is accessible only with
the Service and Engineer logon codes.
Figure 4.9 Control System Service Screen
34 Proprietary and Confidential ©2025 Vertiv Group Corp. 4 Operation
Vertiv™ CoolChip CDU 600 Operation and Maintenance Guide