On-Off Charger
It will show “Turn on Charger?” when the charger is off. It will show “Turn off Charger?” when the charger is on. Touch “YES” to
turn on or off the charger. Or touch “NO” to cancel this operation. Then, the screen will return to the main screen.
Touch “Back” to return to CONTROL screen immediately.
WARNING! This function should be operated only from qualified technicians and only to perform maintenance
operations. During normal operation of the UPS the charger will be automatically turned ON from the UPS. In
case the charger is manually turned ON through this command, it will be necessary then to turn OFF and ON
the UPS in order to restore the automatic operation of the charger. If this UPS restart is not performed, a
battery damage can occur.
Figure 3.19 Turn ON Charger Screen
Figure 3.20 Turn Off Charger Screen
40 Proprietary and Confidential ©2024 Vertiv Group Corp. 3 Operations
Vertiv™ Liebert® MTP Online UPS User Manual 20-40-80kVA