REV : 13
REV DATE : 2/18
DPN002340
Page :1 /1
DA125, DA150 & DA165 W/ LIEBERT MC
Form No.: DPN001040_REV4
PIPING SCHEMATIC
LIEBERT DSE
Electronic
Expansion
Valve
LIEBERT MC CONDENSER
HOT GAS DISCHARGE
LIQUID
EVAPORATOR
COIL
SUCTION
Check
Valve
Trap at base of risers
over 5ft. (1.5m)*
LIQUID RETURN
HOT GAS DISCHARGE
For rises over
25ft. (7.6m), trap
every 20ft. (6m)
or evenly divided*
Optional "EconoPhase" UNIT
Ball Valve
Ball Valve
Check
Valve
Solenoid
Valve
Notes:
1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
2. Circuit 1 must be maintained between indoor unit, condenser and EconoPhase unit. Circuit 2 must be maintained between indoor unit, condenser and EconoPhase unit.
3. Schematic representation shown. Do not use for specific connection locations.
4. The outlet of the receiver must be higher than the elevation of the EEV inside the indoor unit. This vertical height must not exceed 60ft. (18.3m). Liebert DSE Receiver required
for systems with or without EconoPhase.
5. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum thickness. All outdoor insulation must be UV and ozone resistant.
6. Components are not supplied by Liebert but are required for proper circuit operation and maintenance.
7. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid flood back to compressor. Pitch horizontal gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
8. Do not isolate any refrigerant circuits from over pressurization protection.
Service
Valve
Service
Valve
LIEBERT DSE
Check
Valve
Liquid from Condenser
Hot Gas Discharge from Indoor Unit
Liquid to Indoor Unit
Includes Factory traps.
No external trap required.
LIEBERT DSE
RECEIVER
Differential
Check Valve
Differential
Check Valve
SERVICE/SCHRADER (ACCESS) CONNECTION, WITH VALVE CORE.
FIELD PIPING
FACTORY REFRIGERANT PIPING
SERVICE/SCHRADER (ACCESS) CONNECTION, NO VALVE CORE.
Field installed relief valves
required for 50Hz EU CE
units rated maximum
650 PSIG (45 bar)
2
2
6
6
6
Filter Drier
2
2
2
INTERCONNECTING
PIPING
LIEBERT MC WITH DSE RECEIVER
AND OPTIONAL ECONOPHASE
Pressure Transducer
Sight
Glass