Humidity Sensor BAdjusts the humidity reading from the actual remote sensor designated Sensor B to
compensate for any error of the sensor or to match other sensors in the room.
Calibrated Humidity Sensor BDisplays the adjusted humidity value of the remote CAN Temp Humidity
sensor designated as Sensor B. This value is the actual sensor reading plus or minus the offset Humidity
Sensor B.
Figure 6.40 Sensor calibration/Setup, page 2 of 3
Supply Refrigerant Sensor—Adjusts the temperature reading from the actual supply refrigerant sensor
to compensate for any error of the sensor.
Calibrated Supply Refrigerant SensorDisplays the adjusted temperature value of the supply refrigerant
sensor. This value is the actual sensor reading plus or minus the offset Supply Refrigerant Sensor.