High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The range for the
high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F(26.7°C).
Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range for the
low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the high room
dewpoint alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature—Sets the threshold for a high a refrigerant temperature alarm. The range
for the high supply refrigerant temperaturealarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F
(26.7°C).
Figure 6.33 Set alarms, page 2 of 7
Customer Input 1—Selects the device and operation of the customer input. Each event reflects a different
alarm and possible action to the unit. Selectable options are:
Comp Lock PD—This parameter will lockout and pump down the compressor
Call Service
C-Input
Water
Smoke
Customer Input 1 active when—Selects whether the input is normally closed or normally open.
WARNING ACTIVATES ALARM RELAY—Sets the alarm relay (K3) to activate when a warning occurs.
Reset Disabled Alarms—Resets disabled events.
Vertiv | Liebert® XDC™ User Manual | 95