6 APPENDICES
The following tables display electrical and physical specifications and also communication interfaces and agency approval.
Appendix A: Specifications
PARAMETER LIMITS
Voltage 7-12 V DC
Power 6.5 W Maximum
Operating Temperature Range, 41 to 140 (5 to +60) °F (°C)
Ambient Storage Temperature Range, -40 to 140 (-40 to +60) °F (°C)
Relative Humidity 0% to 95% (non-condensing)
Maximum Operating Altitude, ft. (m) 6560 (2000)
Dimensions, WxDxH, in. (mm) 4.0 x 0.84 x 1.78 (101.6 x 21.3 x 45.2)
Table 6.1 Electrical and Physical Specifications
COMMUNICATION PORTS DESCRIPTION
Ethernet 2 (one 10/100/1000Mbps Port; one 10/100Mbps Port)
I2C 1 (interface to the RPC BDM)
EIA562 RS-232 1 (interface to Avocent appliances)
1-Wire 1 (interface to Liebert 1-wire sensors)
USB 1 (supports memory stick configuration)
Safety Standards
(Vary by model and region)
IEC 60950-1:2005 (2nd Edition) + Amendment 1:2009
CSA C22.2 NO. 60950-1-07 (2nd Edition) + Amendment 1:2009
UL 60950-1 (2nd Edition) + Amendment 1:2009
IECEE CB Full Certification Scheme
EMC Standards
(Vary by model and region)
FCC Class A, Part 15, Industrial
EN55022:2006+A1:2007, Class A, Industrial
EN55024:1998+A1:2001+A2:2003, Class A, Industrial
IEC61000-3-2:2006, IEC61000-3-3:1995+A1:2001+A1:2005
IEC61000-4-2/3/4/5/6/8/11
Agency Approvals (Vary by model and region) UL, cUL, CE, BV, PSE, CB, RoHS, REACH, WEEE
Table 6.2 Communication Interfaces and Agency Approval
Vertiv | RPC2™ Communications Module Installer/User Guide | 47