LEVEL SETTING DEFAULT VALUE
SNMP
SNMPv1/v2 Enabled
SNMPTraps SNMP V1
SNMPUDP Port 161
SNMPUDPPort 162
Liebert Global Products MIB Enabled
Liebert MIBTraps Enabled
Authentication Traps Enabled
System Notify Trap Enabled
Heartbeat Interval 5 minutes
SNMPv3 Enabled
Web Server
Web Server HTTPS
HTTPPort 80
HTTPs Port 443
Refresh Interval (seconds) 30
Authentication Type Local
Credentials
Admin
Username: admin
Password: admin
Poweruser
Username: pwrusr
Password: pwrusr
Appliance
Username: appliance
Password: rpc2k
PDU
Over Current Alarm Threshold
L1, L2, L3, N
45%
Over Current Warning Threshold
L1, L2, L3, N
40%
Under Current Alarm Threshold
L1, L2, L3
0%
Unbalanced Load Alarm Threshold 0%
Branch
Over Current Alarm Threshold 95%
Over Current Warning Threshold 90%
Under Current Alarm Threshold 0%
Vertiv | RPC2™ Communications Module Installer/User Guide | 51