43
Cause Remedy
The heating system is switched off Turn the ON/OFF switches (see chap-
ter "Controls") at all control units ON.
Switch ON the mains isolator, if instal-
led (outside the boiler room).
Check the fuse/MCB in the power dis-
tribution board (main domestic fuse/
MCB), and reset/replace if required.
Control unit or remote control incorrectly
adjusted.
Check settings and correct if required:
At every Vitotronic 100:
" " must be set (see page 19).
At the Vitotronic 300-K:
"Heating and DHW" must be selec-
ted for the heating circuit (see
page 22).
Room temperature (see page 22).
Time (see page 35).
Time program (see page 23).
Heating curve (see page 53)
Check the settings at the remote con-
trol (if available).
Separate operating instructions
Only when operating with DHW heating:
DHW priority is enabled.
Wait until the DHW cylinder has been
heated up.
Screed function for drying a building is
enabled.
Wait until the building drying time has
elapsed.
No fuel. With fuel oil or LPG:
Check the fuel supply and re-order if
required.
With natural gas:
Open the gas shut-off valve or enquire
with your gas supply utility if required.
"Fault" is displayed at the Vitotronic 300-
K, and the red fault indicator flashes (see
chapter "Controls").
Scan the type of fault, make a note of the
fault code and acknowledge the message
(see page 40).
Contact your local heating contractor if
required.
What to do if...
Rooms are too cold
5592 675 GB