42
Emissions test mode for testing flue gas
with boiler water temperature raised
briefly. This test mode should only be
activated by your flue gas inspector dur-
ing the annual inspection.
Test mode must be activated at the
Vitotronic 100 of the boiler to be tes-
ted and also, for heat transfer, at the
Vitotronic 300-K cascade control unit.
Vitotronic 100, types GC1B and GC4B and Vitotronic 300-K
Move the emissions test switch on both
control units (see chapter "Controls") to
position .
The following functions are activated:
Burner is started.
Note
Burner start-up can be delayed, e.g.
through fuel oil preheating.
All pumps are started.
Mixer remains set to control function
The temperature controller regulates
the boiler water temperature.
Ending emissions test mode
Set the emissions test switch to position
a
.
or
Close the cover flap (see page 9).
Vitotronic 100, type HC1B and Vitotronic 300-K
Press the following keys:
1. for settings; " " flashes.
2.
until " " flashes.
3. OK to confirm; "ON" flashes.
4. OK to confirm.
Ending emissions test mode
Press the following keys:
1. for settings; " " flashes.
2.
until " " flashes.
3. OK to confirm; "OFF" flashes.
4. OK to confirm.
Emissions test mode ends automatically
after 30 min.
Emissions test mode
Emissions test mode
5592 675 GB