Emissions test mode for testing flue gas
with boiler water temperature raised
briefly. This test mode should only be
activated by your flue gas inspector dur-
ing the annual inspection.
Test mode must be activated at the
Vitotronic 100 of the boiler to be tes-
ted and also, for heat transfer, at the
Vitotronic 300-K cascade control unit.
Vitotronic 100, types GC1B and GC4B and Vitotronic 300-K
Move the emissions test switch on both
control units (see chapter "Controls") to
position .
The following functions are activated:
■ Burner is started.
Note
Burner start-up can be delayed, e.g.
through fuel oil preheating.
■ All pumps are started.
■ Mixer remains set to control function
■ The temperature controller regulates
the boiler water temperature.
Ending emissions test mode
Set the emissions test switch to position
a
.
or
Close the cover flap (see page 9).
Vitotronic 100, type HC1B and Vitotronic 300-K
Press the following keys:
1. for settings; " " flashes.
2.
until " " flashes.
3. OK to confirm; "ON" flashes.
4. OK to confirm.
Ending emissions test mode
Press the following keys:
1. for settings; " " flashes.
2.
until " " flashes.
3. OK to confirm; "OFF" flashes.
4. OK to confirm.
Emissions test mode ends automatically
after 30 min.
Emissions test mode
Emissions test mode