EasyManua.ls Logo

Viessmann VITOPLEX 300 Type TX3A - Vitotronic 300-K, type MW1 (System Control); Switching points; 11.2 Components in the delivered condition

Viessmann VITOPLEX 300 Type TX3A
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vitotronic 300-K, type MW1
Vitotronic 300- K
M M
Weather-compensated, digital cascade and heating circuit control unit:
Type MW1S: For installation in control panels (see separate data-
sheet).
For multi-boiler systems
With sequential boiler strategy
For up to two heating circuits with mixer (a further 32 Vitotronic 200-
H heating circuit control units can be connected via the LON).
An extension kit (accessory) is required for each heating circuit with
mixer
In conjunction with the Vitotronic 100, type GC1:
For two-stage or modulating burners, if installed
With cylinder thermostat
or
Control of a cylinder primary system with mixer assembly (only avail-
able as an alternative to the control of a constant return temperature
raising facility with a regulated three-way valve)
With boiler protection functions subject to system version:
Distribution pump
or
Shunt pump
or
Control of a constant return temperature raising facility with a
regulated three-way valve (only available as an alternative to the
control of a cylinder primary system with mixer assembly)
With integral diagnostic system
Programming unit with plain text prompts
Via external contacts:
Heating program changeover
Requirement to default set flow temperature
Blocking the burner
Mixer "Open" or "Closed"
With capability to communicate via LON (LON communication mod-
ule and terminators are part of the standard delivery)
Switching points
G
B
A
20
Flow temperature in °C
75
110
100
90
80
70
60
50
40
30
10
Outside temperature in °C
-50+5+10+15+20
C
D
-20-15-10
F
E
A
Setting options for the high limit safety cut-out of the Vitotronic
boiler control units (delivered condition 110 ºC)
B
Setting options of the control thermostat of the Vitotronic boiler
control units (delivered condition 95 ºC)
C
Low-end boiler water temperature (see operating conditions
page 5 to 11)
D
Burner starting points
E
Burner shutdown points
F
Selected heating curve
G
Set maximum boiler water temperature
11.2 Components in the delivered condition
Allocation to control unit types
Vitotronic 100 200 300 300-K
Type GC1 GW1 GW2 MW1 MW1S
Components
Boiler water temperature sensor x x x
Cylinder temperature sensor x x x x
Outside temperature sensor x x x x
Contact temperature sensor (see acces-
sories)
x x
Control units
(cont.)
OIL/GAS BOILERS
VIESMANN
53
5822 426 GB
11

Table of Contents

Related product manuals