EasyManua.ls Logo

Viessmann VITOPLEX 300 Type TX3A - Connection to on-site control units to the Vitotronic 100, type GC1 in single boiler systems

Viessmann VITOPLEX 300 Type TX3A
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection to on-site control units to the Vitotronic 100, type GC1 in single boiler systems
Operation with a two-stage burner
146
A
B
C
143
1 2 31 2 3
A
Burner stage 1 "ON"
B
Burner stage 2 "ON"
C
External load-dependent starting
A
,
B
and
C
are zero volt contacts of the higher control unit.
External burner start – burner stage 1
Contact at terminals 1 and 2 of plug
aVD
Contact closed:
Burner stage 1 is switched ON.
Burner stage 2 is switched ON only for maintaining the minimum
temperature.
The boiler water temperature is limited by the electronic maximum
temperature limiter (see the Vitotronic 100 service instructions), if it
is set below that of mechanical thermostat "
R
".
Contact open:
Burner stage 1 is switched OFF.
External burner start – burner stage 1 and 2
Contact at terminals 2 and 3 of plug
aVD
Contact closed:
Both burner stages are switched ON.
The boiler water temperature is limited by the electronic maximum
temperature limiter, if it is set below that of mechanical control ther-
mostat "
R
".
Burner stage 2 is switched OFF 2 K sooner.
Contact open:
Burner stages 1 and 2 are switched OFF.
External starting subject to load
The burner is started, subject to load, when the zero volt contact across
terminals "2" and "3" at plug-in connector
aVH
closes.
The boiler will be constantly operated at the set temperature.
The boiler water temperature is limited via the maximum set boiler
water temperature or via the mechanical control thermostat.
The set value is adjusted via code "9b".
Adjustments at the Vitotronic 100
Code "01:1" (delivered condition)
The boiler water temperature must be set to the lower value (see
operating conditions, pages 5 to 11).
The minimum boiler temperature is maintained (see operating con-
ditions, pages 5 to 11).
The cylinder thermostat is activated when the cylinder temperature
sensor is connected.
The high limit safety cut-out settings and other settings depend on
the system equipment level and the safety equipment to EN 12828
or EN 12953.
High limit safety cut-out 110 °C 100 °C
Temperature controller 100 °C 87 °C
Coding address "06" for electronic max-
imum temperature limit (Vitotronic 100)
95 °C 85 °C
Maximum temperature of the on-site
control unit
90 °C 80 °C
Note
A safety temperature of 120 °C (EN12953) is only permissible with
an additional, self-monitoring high limit safety cut-out. For an acces-
sory pack for safety temperature 120 ºC, see Viessmann pricelist.
Operation with a modulating burner
143
1 2 3
A
41
41
E
90
90
B
C
D
BU
BK
BN
BU
BK
BN
A
Plug to the control unit
B
Burner stage 1 (base load) "ON"
C
Reduce burner output (modulation controller)
D
Raise burner output (modulation controller)
E
Plug to the burner
Colour coding to DIN IEC 60757
BK black
BN brown
BU blue
Control units
(cont.)
72
VIESMANN
OIL/GAS BOILERS
11
5822 426 GB

Table of Contents

Related product manuals