Chapter 5 238-2BC00 - Combination module Manual VIPA System 200V
5-30 HB97E - SM-AIO - Rev. 12/32
Main counting direction backwards
The counter counts starting with the load value.
When the counter reaches the end value in negative direction, it jumps
to the load value at the next negative count pulse.
You may exceed the upper count limit.
Valid value range
Limit value - 2 147 483 647 (-2
31
+1) to + 2 147 483 647 (2
31
-1)
Upper count limit +2 147 483 647 (2
31
-1)
Counter value - 2 147 483 647 (-2
31
+1) to +2 147 483 647 (2
31
-1)
Load value - 2 147 483 647 (-2
31
+1) to +2 147 483 647 (2
31
-1)
upper
counter limit
load value
0
gate start
time
counter value
gate stop
end value